1.It is a new generation of multi-functional computer temperature controller
2.It is designed according to JB/T7631 standard
3.It adopts the most advanced German RISC monolithic computer combined with advanced 12C storage and adjustment technology.
4.It can record the temperature of the three winding package before power failure and the working state of the machine.
Chat Now

Product Details

It is a new generation of multi-functional computer temperature controllers designed for reliable operation of air-cooled dry-type power transformers. The temperature controller is designed according to JB/T7631 standard by adopting the most advanced German RISC monolithic computer combined with advanced 12C storage and adjustment technology. At the same time, the thermostat also has a “black box” function, which can record the temperature of the three winding package before power failure and the working state of the machine.


Technical Parameter

Environment Temperature: -10℃~+55℃

Environment Humidity: 90%

Voltage: 220VAC (+10%, -15%)

Frequency: 50Hz or 60Hz (±2Hz)

Measure Scope: -30.0℃~240.0℃

Accuracy: ±1%FS (Controller 0.5%, Sensor 0.5%)

Resolution: 0.1℃

Fan(cooling) contact capacity: 6A/250VAC

Control output capacity: 6A/250VAC; 6A/30VDC(Resistive load)

Power: ≤8W


Standard

Production Standard: JB/T 7631-2005《Resistive Thermometers of Transformers》

Passed Certification Standard: ISO9001:2000 International Quality System Certification

Passed Testing Standard: IEC61000-4:1995 International Standard and GB/T 17626-2008Electromagnetic Compatibility Testing and Measurement Techniques》 


1. NJ(BWDK)S Series Dry-type Transformer Temperature controller is an intelligent controller designed for the safe operation of dry-type transformer. The temperature controller uses single-chip microcomputer technology and uses three platinum thermal resistors embedded in three-molybdenum winding of dry-type transformer to detect and display the temperature rise of transformer winding automatically. The forced air cooling of the winding by the start-stop cooling fan can avoid or reduce the faults caused by the over-temperature departure of the transformer, and can control the over-temperature alarm and the over-temperature tripping output to ensure the safe operation of the transformer, thereby prolonging the service life the transformer.

Technical characteristics

Working Voltage

220VAC. 380VAC or 220VDC(10%, -15%) can be customized according to user needs

Working environment

-10℃-55℃﹤90%RH

Measuring arrange

-30.0℃-240℃

Temperature precision

+1%FS(thermostat 0.5 level, Sensor 0.5 level)

Power waste

≤8W

Resolving power

0.1℃

Fan output total capacity

6A/250VAC

Control output total

6A/250VAC; 6A/30VDC

Electrical strength

Between outer and terminals≥2000V

Insulation performance

Between outer and terminals≥500MΩ


NJS(Temperature controller) Level A series terminal wiring Diagram

image

Note:(1) fan contact capacity: 10A/250VAC  control output contacts: 5A/250VAC;5A/30VDC(resistive);

(2) 3 and 4 are F type endemic 13,14 G,I type endemic 7,8,9,10,11 are E type endemic


NJS(Temperature controller) Level B series terminal wiring Diagram

image

Note:(1) fan contact capacity: 10A/250VAC  control output contacts: 5A/250VAC;5A/30VDC(resistive);

(2)3 and 4 are F type endemic 13,14 G,I type endemic 7,8,9,10,11 are E type endemic


2. NJ(BWDK)Q Series Dry-type Transformer Temperature Controller is an intelligent controller designed for the safe operation of dry-type transformer. The temperature controller  uses single-chip microcomputer technology and uses three platinum thermal resistors embedded in the three-phase winding of dry-type transformer to detect and display the temperature rise of the transformer winding automatically. The winding is forced to be cooled by the start-stop cooling fan to avoid or reduce the faults caused by the excessive temperature of the transformer and to control the over-temperature alarm and the over-temperature tripping output so as to ensure the safe operation of the transformer and prolong the service life of the transformer

Technical characteristics

Working Voltage

220VAC. 380VAC or 220VDC(10%, -15%) can be customized according to user needs

Working environment

-10℃-55℃﹤90%RH

Measuring arrange

-30.0℃-240℃

Temperature precision

+1%FS(Temperature controller 0.5 level, Sensor 0.5 level)

Power waste

≤8W

Resolving power

0.1℃

Fan output total capacity

6A/250VAC

Control output total

6A/250VAC; 6A/30VDC

Electrical strength

Between outer and terminals≥2000V

Insulation performance

Between outer and terminals≥500MΩ

 

Terminal wiring diagram

image

(1)Terminal 1 and 2 external AC 220V working power supply (terminal 1 is connected to zero line)

(2)Terminals 5,6 and 3,4 are respectively connected with two phase fan (Power supply)

(3)Terminals 7 and 9 are over temperature alarm signals, often output contacts.

(4)Terminals 11 and 13 are frequently opened output contacts for over temperature trip signals.

(5)Terminals 15 and 17 fail to alarm and often open output contacts

(6)Terminals 19 and 21 are constant output contacts for external transformer cabinet threshold

(7)Terminals 8 and 10 are commonly used output contacts for fan cooling.

(8)Chains 8 and 10 are normally ope output contacts for iron core alarm signals.

(9)Terminals 12, 14 and 16, 18 are universal terminal signals, normally open output contacts

(10)Terminals 23 and 24 are RS485 through floor terminals

(11)Termianl 25-29 are 4~20mA analog current output terminal.


3. NJ(BWDK)Q Series Dry-type Transformer Temperature Controller is an intelligent controller designed for the safe operation of dry-type transformer. The temperature controller uses single-chip microcomputer technology and uses three platinum thermal resistors embedded in the three-phase winding of dry-type transformer to detect and display the temperature rise of the transformer winding automatically. The winding is forced to be cooed by the start-stop cooling fan to avoid or reduce the faults caused by the excessive temperature of the transformer and to control the over-temperature alarm and the over-temperature tripping output so as to ensure the safe operation of the transformer and prolong the service life of the transformer

Technical characteristics

Working Voltage

220VAC. 380VAC or 220VDC(10%, -15%) can be customized according to user needs

Working environment

-10℃-55℃﹤90%RH

Measuring arrange

-30.0℃-240℃

Temperature precision

+1%FS(Temperature controller 0.5 level, Sensor 0.5 level)

Power waste

≤8W

Resolving power

0.1℃

Fan output total capacity

6A/250VAC

Control output total

6A/250VAC; 6A/30VDC

Electrical strength

Between outer and terminals≥2000V

Insulation performance

Between outer and terminals≥500MΩ

Terminal wiring diagram

image

(1) Terminal 1 and 2 external AC 220v working power supply (terminal 1 is connected to zero line)

(2) Terminals 5,6 and 3,4 are respectively connected with two phase fan(Power supply)