ZN85-40.5 VCB/ Vacuum circuit breaker

ZN85-40.5 VCB/ Vacuum circuit breaker

1.With the voltage of 40.5kV is three-phase AC, 50/60 Hz indoor power distribution equipment.
2.It’s used for switchgear KYN61-40.5(Z)
3.It’s accordance with GB1984 AC HV vacuum circuit breaker standard.
4.It effectively reduces the dimensions of VCB, the overall arrangement is reasonable and simple,with aesthetic appearance.
5.It has high reliable with characteristics of long life and easy maintenance and free-maintenance for operating mechanism.
6.Meet the “Five Preventions” function.
Chat Now

Product Details

ZN85-40.5 series indoor high voltage vacuum circuit breaker is suitable for power system with rated voltage 40.5kV and three-phase AC 50 / 60Hz. The operating mechanism adopts a spring mechanism specially designed for this new type of circuit breaker, with high reliability and long service life; composite insulation is used to meet the insulation requirements under normal operating conditions; the circuit breaker handcart uses a screw nut propulsion mechanism device with a There is an overrunning clutch, which can easily move the handcart in the switch cabinet, so that the stroke range of the handcart is accurate and reliable; it is equipped with a forced mechanical lock to meet the requirements of the switchgear "five anti-interlocking" interlocking function. The circuit breaker is used in conjunction with KYN61-40.5 switchgear and is suitable for the control and protection of power transmission and distribution systems such as power plants and substations. The product design meets the requirements of GB 1984 "High Voltage AC Circuit Breaker"


Features:

1. Light and reliable operation: Combined with the advantages of the 40.5kV voltage level circuit breaker handcart propulsion mechanism at home and abroad, a flexible and reliable propulsion interlocking mechanism with optimized design, equipped with electrical and mechanical dual-channel anti-misoperation devices, is portable, safe and reliable.

2. High rated current: new large-capacity vacuum arc extinguishing chamber is selected, and advanced equipment is used to control the quality and thickness of the silver plating of the conductive loop to ensure a low main loop resistance and the maximum rated current of 2500A.

3. Strong corrosion resistance: The internal parts of the operating mechanism adopt advanced surface treatment technology to make the parts have stronger corrosion resistance and higher mechanical stability.

4. Complete cabinet distribution scheme: it can be equipped with standard KYN61 switchgear (1400mm wide) or small KYN61A switchgear (1200mm wide); high prototype can be equipped with 1600mm or 1680mm cabinet

5. High interchangeability: the use of advanced assembly tooling and cabinet inspection tooling to ensure that the circuit breaker has good consistency and cabinet interchangeability.


Applying ambient conditions

1. Ambient temperature: Max. Temperature: +40℃, and average temperature daily should be no more than 35℃. Min. Temperature: -15℃.

2. Relative humidity: average relative humidity daily: ≤95%, average relative humidity monthly: ≤90%, average vapour pressure daily: ≤2.2kPa, average vapour pressure monthly: ≤1.8kPa

3. Altitude above sea level: no more than 2000m;

4. Earthquake intensity: not exceed 8 degrees.

5. It should be installed in condition without obvious dust, fire, chemical erosion, vapor and salt spray.


Item

Unit

Value

Rated voltage

kV

40.5

Rated frequency

Hz

50/60

Rated power frequency withstand voltage(1min)

kV

95

Rated lightning impulse withstand voltage(peak)

kV

185

Rated current

A

630

1250

1600

2000

2500

3150

Rated short circuit breaking current

Rated short time withstand stable current

4s rated short time withstand current

kA

25

25

25





31.5

31.5

31.5

31.5

31.5

Rated short circuit closing current(peak)

Rated peak withstand current

Rated dynamic stable current

kA

63

63

63





80

80

80

80

80

Breaking times of short circuit breaking current

times

20

Rated thermal stability time

s

4

Rated operating sequence


O-0.3s-CO-180s-CO

Mechanical life

times

10000

Rated operating voltage

V

DC110/220  AC110/220


Hot Tags: ZN85-40.5 VCB/ Vacuum circuit breaker, China, suppliers, manufacturers, factory, company, agent, distributor, products

Inquiry

You Might Also Like